Perth's Fujitsu fault code lookup
Fujitsu fault codes decoded
105 codes covered — what each one means, the likely cause, and whether it's worth trying something yourself before booking. Compiled from Fujitsu General documentation.
Fujitsu General systems report faults two ways: as a two-part code on wired wall controllers and newer displays (11, 42, A4…), or — on wall-mounted splits without a display — as counted flash patterns on the indicator lamps. Both are covered below for the residential range: wall splits, multi-splits and ducted systems.
How to find your Fujitsu fault code
Wall splits without a display — count the flashes
- 1 A rapidly flashing Economy lamp means a fault is stored.
- 2 Watch the Operation and Timer lamps — they flash in counted bursts, with a pause of a few seconds between rounds.
- 3 Count one burst: Operation flashes give the first digit, Timer flashes the second. Operation 4 + Timer 2 = code 42.
- 4 On the newest series the Timer lamp carries the first digit and the Economy lamp the second — if your count matches nothing in the table, try reading it the other way.
Wired & wall controllers (ducted and cassettes)
- 1 EE:EE on an older hardwired controller means a fault is stored — it’s the prompt, not the fault.
- 2 Hold the Energy Save + Zone Control buttons together for 3+ seconds — the actual code (e.g. E:41) appears on the LCD. Same buttons to exit.
- 3 Newer backlit controllers and anywAIR touchscreens show the two-part code directly on screen. (anywAIR “FG” codes relate to the controller and Wi-Fi, not the refrigeration system.)
Older models — self-diagnosis from the remote
- 1 Stop the unit, then hold both set-temperature buttons on the remote for 5+ seconds.
- 2 The self-diagnosis code appears on the remote’s LCD — hold the same buttons for 5 seconds to exit.
Fujitsu fault code tables
Two-part controller codes — current residential series (wall-mounted splits, multi-splits, ducted with wired controller)
| Code | What it means | Likely cause | What to do |
|---|---|---|---|
| 3A | Indoor unit communication circuit (wired remote controller) error | Failure of the remote-controller communication circuit on the indoor PCB, or damaged/shorted controller cabling | Book a service |
| 5U | Indoor unit error (unspecified) | Indoor unit fault that does not map to a more specific code; often indoor PCB related | Book a service |
| 6A | Display PCB communication error | Communication failure between the outdoor main PCB microcomputer and the display/sub PCB; PCB or interconnect fault | Book a service |
| 9A | Outdoor unit coil (electronic expansion valve) error | EEV coil open-circuit, disconnected coil connector, or valve drive fault | Book a service |
| 9U | Outdoor unit error (unspecified) | Outdoor unit fault that does not map to a more specific code; often outdoor PCB related | Book a service |
| 11 | Serial communication error — indoor and outdoor units have stopped talking to each other | Loose or damaged interconnect wiring between indoor and outdoor units, power glitch, or a failing PCB | Try this first Power cycle at the breaker: switch the AC circuit off for at least 5 minutes, then back on. If the code returns, book a service call — do not open wiring covers yourself. |
| 12 | Wired remote (wall) controller communication error — controller can't talk to the indoor unit | Controller cable fault, loose terminals, or controller/PCB failure. Note: on the newest 2024+ R32 series Fujitsu lists 12 as an outdoor serial communication error | Try this first Power cycle at the breaker for 5 minutes. If the wall controller stays blank or the code returns, book service. |
| 15 | Check run (installer test run) not completed | System was never test-run after installation, or test run was interrupted | Book a service |
| 18 | External communication error — indoor unit has lost communication with the WLAN (Wi-Fi) adapter or an external controller/interface | Wireless LAN adapter fault or dropout, loose adapter connector/wiring, router or network outage, or external interface PCB fault. Confirmed in the official Fujitsu service manual (ASUG09LZAS) and both Australian service references. Increasingly common now Wi-Fi control kits are fitted to residential splits. | Try this first |
| 21 | Connection wiring/piping count error (multi-split setup) | Indoor units wired/piped to the wrong ports or mismatched during installation | Book a service |
| 22 | Indoor unit capacity error (multi-split) | Connected indoor unit capacity outside what the outdoor unit supports | Book a service |
| 23 | Connected combination error (multi-split) | Incompatible indoor/outdoor model combination configured | Book a service |
| 24 | Connection unit number error — the number of indoor units (Simultaneous Multi) or indoor/branch units (Flexible Multi) doesn't match the system configuration. | Indoor unit not powered or not communicating, wiring fault between units, or incorrect multi-split setup. | Book a service |
| 26 | Indoor unit address setting error | Duplicated or incorrect indoor unit address on multi-split or wired-controller systems, typically after PCB replacement or incorrect commissioning/DIP-switch setup | Book a service |
| 27 | Master/slave unit set-up error | Incorrect master/slave designation where two wired remote controllers or grouped indoor units are configured; commissioning/settings fault | Book a service |
| 29 | Connection unit number error in wired remote controller system | More indoor units connected to the remote controller circuit than the system supports, or unit-count mismatch after wiring changes | Book a service |
| 31 | Indoor unit model information / EEPROM memory error | Corrupted indoor PCB memory, often after severe power disturbance | Book a service |
| 32 | Indoor unit main PCB error | Failed indoor circuit board or its power supply | Book a service |
| 35 | Manual auto switch error — the button on the indoor unit reads as stuck | Manual auto button jammed or held in (often after the front panel is refitted), or switch failure | Try this first Check the front panel is seated properly and nothing is pressing the manual auto button, then power cycle at the breaker. If it returns, book service. |
| 41 | Indoor room temperature sensor (thermistor) fault | Sensor open/short circuit or unplugged connector | Book a service |
| 42 | Indoor heat exchanger (coil) temperature sensor fault | Coil thermistor open/short circuit | Book a service |
| 51 | Indoor unit fan motor error — the indoor blower isn't spinning as commanded | Blower obstruction, heavily clogged filters loading the motor, seized bearing, or motor/PCB failure. Note: newest 2024+ series tables list 51 as outdoor fan motor 1 | Try this first Isolate power, clean the return-air filters and check the blower wheel spins freely with nothing caught in it. If the code returns, book service. |
| 53 | Drain error / water drain abnormal — the float switch has detected condensate backing up | Blocked or kinked condensate drain, failed drain pump (ducted/cassette), or drain running uphill | Try this first Check where the drain discharges outside and clear any blockage or kink; make sure the hose falls continuously. Power cycle after clearing. If water still backs up or the code returns, book service before ceiling/wall damage occurs. |
| 57 | Indoor unit damper error (ducted/cassette models) | Damper motor failure, jammed damper, or limit-switch/position-detection fault | Book a service |
| 58 | Indoor unit intake grille position error | Intake grille or filter access panel not fully closed/seated (often after filter cleaning), or grille safety-switch fault. Listed in the official service manual; a common customer-resolvable code | Try this first |
| 62 | Outdoor unit main PCB error — model information or communication fault, often EEPROM-related. | Defective outdoor main PCB or corrupted board memory. (Inverter error is the separate code 63.) | Book a service |
| 63 | Inverter error — the outdoor drive electronics have faulted | Inverter PCB fault, voltage problems, or compressor winding issue | Book a service |
| 64 | Active filter / PFC (power factor) circuit error | Power supply electronics fault on the outdoor PCB, sometimes triggered by poor mains voltage | Book a service |
| 65 | IPM error — the intelligent power module driving the compressor has faulted | Power module overheating or failure, compressor overload | Book a service |
| 71 | Discharge pipe temperature sensor fault (outdoor) | Thermistor open/short circuit on the compressor discharge line | Book a service |
| 72 | Compressor temperature sensor fault | Compressor thermistor open/short circuit | Book a service |
| 73 | Outdoor heat exchanger (liquid outlet) temperature sensor fault | Coil thermistor open/short circuit | Book a service |
| 74 | Outdoor air temperature sensor fault | Ambient thermistor open/short circuit | Book a service |
| 75 | Suction gas temperature sensor fault | Suction line thermistor open/short circuit | Book a service |
| 76 | Heat sink temperature sensor fault (inverter cooling) | Heat sink thermistor open/short circuit | Book a service |
| 77 | Heat sink temperature sensor error — the thermistor on the outdoor unit's inverter heat sink has failed (open or short circuit). | Failed heat sink thermistor or outdoor inverter PCB fault. (The 2-way/3-way valve temperature sensor fault is code 76.) | Book a service |
| 82 | Sub-cool heat exchanger gas thermistor fault (inlet/outlet) | Sensor open/short circuit on the sub-cooling circuit | Book a service |
| 83 | Liquid pipe temperature sensor error (outdoor unit). | Failed liquid pipe thermistor, loose connector, or outdoor PCB fault. | Book a service |
| 84 | Current sensor error — outdoor unit can't read compressor current correctly | Current transformer fault on the outdoor PCB | Book a service |
| 86 | Pressure sensor / high-pressure switch error | Failed pressure sensor or switch, blocked outdoor coil, refrigerant overcharge or restriction | Book a service |
| 94 | Overcurrent trip — the compressor is drawing too much current and the system cut out to protect itself | Compressor overload, low/unstable supply voltage, failing inverter or compressor | Book a service |
| 95 | Compressor control error — the compressor motor position can't be detected (compressor won't start or stalls) | Seized or failing compressor, inverter drive fault | Book a service |
| 97 | Outdoor unit fan motor error | Fan blocked by leaves/debris, seized bearing, or DC fan motor/PCB failure | Try this first Isolate power and check nothing (leaves, mulch, ice, a bag) is jamming the outdoor fan and the coil isn't buried in debris. Restore power. If the fan still won't spin or the code returns, book service. |
| 98 | Outdoor unit fan motor 2 error | Second outdoor fan motor locked, failed, or speed-feedback fault on larger twin-fan outdoor units | Book a service |
| 99 | 4-way valve error — the system can't switch correctly between heating and cooling | Stuck or failed reversing valve or its solenoid coil | Book a service |
| A1 | Discharge temperature error — the compressor is running dangerously hot | Most often refrigerant undercharge (leak), restriction, or failed discharge sensor | Switch off & call |
| A3 | Compressor temperature error — compressor body over temperature | Refrigerant shortage, poor outdoor airflow, or compressor fault | Book a service |
| A4 | Abnormal high pressure error | Blocked or dirty outdoor coil, outdoor fan failure, refrigerant overcharge, or restricted airflow causing high-pressure protection to trip | Book a service |
| A5 | Low pressure error — refrigerant pressure too low to run safely | Refrigerant leak or blocked/restricted circuit | Book a service |
Wall-mounted split LED flash patterns (Operation / Timer / Economy lamps — models without a code display)
| Code | What it means | Likely cause | What to do |
|---|---|---|---|
| Operation 1 + Timer 1 | Serial communication error between indoor and outdoor units (code 11) | Interconnect wiring fault or PCB comms failure | Try this first Switch the AC off at the breaker for 5 minutes, then retry. If the pattern returns, book service. |
| Operation 1 + Timer 2 | Wired remote controller communication error (code 12) | Controller cable or controller fault | Try this first Power cycle at the breaker for 5 minutes; if it returns, book service. |
| Operation 2 + Timer 1–4 | Multi-split installation/configuration error — unit number / refrigerant circuit address setting error (Simultaneous Multi), indoor capacity (2-2), combination (2-3), or unit count (2-4) | Installation configuration mismatch on a multi-split system | Book a service |
| Operation 3 + Timer 1 | Indoor unit model information / EEPROM error (code 31) | Corrupted indoor board memory | Book a service |
| Operation 3 + Timer 5 | Manual auto switch error (code 35) | Stuck manual auto button on the indoor unit | Try this first Re-seat the front panel, make sure the manual button isn't jammed, then power cycle at the breaker. |
| Operation 4 + Timer 1 | Indoor room temperature sensor fault (code 41) | Thermistor open/short circuit | Book a service |
| Operation 4 + Timer 2 | Indoor heat exchanger (coil) sensor fault (code 42) | Coil thermistor open/short circuit | Book a service |
| Operation 5 + Timer 1 | Indoor unit fan motor error (code 51) | Blower obstruction, clogged filters, or motor failure | Try this first Isolate power, clean filters, check the blower wheel spins freely; book service if the pattern returns. |
| Operation 5 + Timer 3 | Drainage error — condensate not draining (code 53) | Blocked drain line or failed float switch/drain pump | Try this first Clear the outdoor end of the condensate drain and check the hose falls continuously, then power cycle. Book service if it returns. |
| Operation 6 + Timer 1–5 | Outdoor unit electronics fault — model info (6-1), inverter (6-2), active filter (6-4), IPM power module (6-5) | Outdoor PCB / inverter drive failure | Book a service |
| Operation 7 + Timer 1–7 | Outdoor sensor fault — discharge (7-1), compressor (7-2), heat exchanger liquid (7-3), outdoor air (7-4), suction gas (7-5), heat sink (7-6), valve (7-7) thermistor | Sensor open/short circuit or unplugged connector | Book a service |
| Operation 8 + Timer 2–6 | Outdoor sensing fault — sub-cool gas thermistors (8-2), liquid pipe thermistor (8-3), current sensor (8-4), pressure sensors / high-pressure switch (8-6) | Failed sensor, or a genuine pressure problem tripping the switch | Book a service |
| Operation 9 + Timer 4 | Overcurrent trip (code 94) | Compressor overload or inverter fault | Book a service |
| Operation 9 + Timer 5 | Compressor control error — compressor won't start/stalls (code 95) | Seized compressor or drive fault | Book a service |
| Operation 9 + Timer 7 | Outdoor fan motor error (code 97) | Jammed or failed outdoor fan | Try this first Isolate power and clear leaves/debris/ice from the outdoor fan and coil; book service if the fan still won't run. |
| Operation 9 + Timer 9 | 4-way (reversing) valve error (code 99) | Stuck reversing valve — can't change between heating and cooling | Book a service |
| Operation 10 + Timer 1 | Discharge temperature error — compressor running too hot (code A1) | Usually refrigerant undercharge from a leak | Switch off & call |
| Operation 10 + Timer 3 | Compressor temperature error (code A3) | Refrigerant shortage or compressor fault | Book a service |
| Operation 10 + Timer 5 | Low pressure error (code A5) | Refrigerant leak or restriction | Book a service |
| Operation 13 + Timer 2 | Branch box error (multi-split systems with branch boxes) | Branch box communication or control fault | Book a service |
| Operation 5 + Timer 15 | Indoor unit error (LED equivalent of code 5U) | Unspecified indoor unit fault on LED-only wall-mounted models | Book a service |
| Operation 6 + Timer 10 | Display PCB microcomputer communication error (LED equivalent of code 6A) | Communication failure between main and display PCBs | Book a service |
Older ducted/cassette hardwired wall controller codes (EE:EE readout)
| Code | What it means | Likely cause | What to do |
|---|---|---|---|
| E0:00 | Communication error — indoor unit to wall controller | Controller cable fault or controller failure | Try this first Power cycle at the breaker for 5 minutes; if the controller still shows the code, book service. |
| E1:00 | Communication error — indoor unit to outdoor unit | Interconnect wiring or PCB fault | Try this first Power cycle at the breaker for 5 minutes; book service if it returns. |
| E2:00 | Return air temperature sensor open circuit | Failed or disconnected return air thermistor | Book a service |
| E3:00 | Return air temperature sensor short circuit | Failed return air thermistor | Book a service |
| E4:00 | Indoor coil sensor open circuit | Failed or disconnected indoor coil thermistor | Book a service |
| E5:00 | Indoor coil sensor short circuit | Failed indoor coil thermistor | Book a service |
| E6:00 | Outdoor coil sensor open circuit | Failed or disconnected outdoor coil thermistor | Book a service |
| E7:00 | Outdoor coil sensor short circuit | Failed outdoor coil thermistor | Book a service |
| EA:00 | Outdoor ambient (air) sensor open circuit | Failed or disconnected outdoor air thermistor | Book a service |
| EE:00 | High pressure problem — refrigerant pressure too high, system cut out to protect itself | Blocked outdoor coil/airflow, outdoor fan failure, overcharge or restriction | Switch off & call |
| EF:00 | Discharge pipe temperature too high — compressor overheating, classically a sign the system is short of gas | Refrigerant leak/undercharge or restriction | Switch off & call |
| Eb:00 | Outdoor ambient (air) sensor short circuit | Failed outdoor air thermistor | Book a service |
| Ec:00 | Discharge pipe sensor open circuit | Failed or disconnected discharge thermistor | Book a service |
| Ed:00 | Discharge pipe sensor short circuit | Failed discharge thermistor | Book a service |
Older wireless-remote models — self-diagnosis codes shown on the remote LCD
| Code | What it means | Likely cause | What to do |
|---|---|---|---|
| 00 | Communication error — indoor unit to remote controller | Signal/receiver fault or PCB issue | Try this first Replace remote batteries and power cycle the unit at the breaker for 5 minutes; book service if it persists. |
| 0A | Outdoor air temperature sensor open circuit | Failed/disconnected outdoor thermistor | Book a service |
| 0E | Outdoor high pressure abnormal — system cut out on high refrigerant pressure | Blocked outdoor coil, failed outdoor fan, overcharge or restriction | Switch off & call |
| 0F | Discharge pipe temperature abnormal — compressor running too hot, typically short of gas | Refrigerant leak/undercharge | Switch off & call |
| 0b | Outdoor air temperature sensor short circuit | Failed outdoor thermistor | Book a service |
| 0c | Discharge pipe sensor open circuit | Failed/disconnected discharge thermistor | Book a service |
| 0d | Discharge pipe sensor short circuit | Failed discharge thermistor | Book a service |
| 01 | Communication error — indoor unit to outdoor unit | Interconnect wiring or PCB fault | Try this first Power cycle at the breaker for 5 minutes; book service if the code returns. |
| 02 | Room temperature sensor open circuit | Failed/disconnected room thermistor | Book a service |
| 03 | Room temperature sensor short circuit | Failed room thermistor | Book a service |
| 04 | Indoor heat exchanger sensor open circuit | Failed/disconnected coil thermistor | Book a service |
| 05 | Indoor heat exchanger sensor short circuit | Failed coil thermistor | Book a service |
| 06 | Outdoor heat exchanger sensor open circuit | Failed/disconnected outdoor coil thermistor | Book a service |
| 07 | Outdoor heat exchanger sensor short circuit | Failed outdoor coil thermistor | Book a service |
| 08 | Power source connection error | Wiring/supply connection problem to the outdoor unit | Book a service |
| 09 | Float switch operated — condensate water has backed up | Blocked condensate drain or failed drain pump | Try this first Check and clear the condensate drain outlet and confirm the hose falls continuously; power cycle after clearing. Book service if it trips again. |
| 11 | Model information abnormal | PCB configuration/memory fault | Book a service |
| 12 | Indoor fan abnormal | Blower obstruction or fan motor failure | Try this first Isolate power, clean filters and check the blower wheel spins freely; book service if the code returns. |
| 13 | Outdoor signal abnormal | Communication/wiring fault to the outdoor unit | Book a service |
| 14 | Outdoor EEPROM abnormal | Corrupted outdoor board memory | Book a service |
No matching code found.
Meanings vary by series and some codes are model-specific — call 0434 951 341 with the code and your model number and we'll decode it.
Reference compiled from Fujitsu General service and operation documentation. Codes and meanings are provided as general guidance for the Australian residential range and can differ between model series; no affiliation with Fujitsu General is implied.
Tell us the code when you book — diagnosis starts before we arrive
Air conditioning service and repairs across Perth from $220 inc GST — all brands, splits and ducted. Quoting the fault code gives us a head start on where to look; we then test and confirm the actual fault on site before any part is ordered, so you never pay for a part you didn't need.
Frequently Asked Questions
How do I read the flashing lights on my Fujitsu wall split?
When a fault is present the Economy lamp flashes rapidly and continuously, while the Operation and Timer lamps flash in counted bursts with a pause between rounds. Count the flashes in one burst: Operation flashes give the first digit and Timer flashes the second — so Operation 4 + Timer 2 means code 42. The LED pattern table below lists the common patterns directly.
What does EE:EE mean on my Fujitsu controller?
EE:EE on a wired wall controller means a fault is stored — it's the prompt, not the fault itself. Older ducted controllers then display the actual code when you hold the zone/set buttons (varies by controller); the code that appears is what you look up in the tables above.
Can I reset a Fujitsu fault code?
Switching the system off at the isolator or breaker for two minutes clears many one-off trips — a safe first step for anything marked “Try this first”. If the code or flash pattern comes back, the fault is genuine and worth diagnosing properly before it grows.
My model shows different codes to this list — why?